Heat pumps Double storage tank WP-VA-Kombi 200/80 stainless steel dwh tank with Buffer tank
![](images/shop/artikel/100602000-01_2000.jpg)
![](images/shop/artikel/100602000-02_2000.jpg)
![](images/shop/artikel/100602000-03_2000.jpg)
![](images/shop/artikel/100602000-01_200.jpg)
![](images/shop/artikel/100602000-02_200.jpg)
![](images/shop/artikel/100602000-03_200.jpg)
incl. VAT 19% for shipping to Germany
plus shipping costs
Heat pump combination tank WP-VA-KOMBI
with integrated stainless steel domestic
hot water (DHW) tank with 200 litres
and buffer tank with 80 litres. The
large stainless-steel heat exchanger in
the DHW tank ensures very efficient heat
transfer and a high hot water output.
The corrosion resistant stainless-steel
DHW tank is characterised by its low
weight and the hygienic and food-safe
surface quality. Cleaning flange and
connection for circulation and immersion
heater included. The buffer tank made of
steel with connection for an immersion
heater makes the tank a compact
all-in-one solution. It serves as a
hydraulic separator for a heat pump.
The high-quality hard foam thermal
insulation minimises energy losses.
Technical data:
height with insulation: 1780 mm
tilted height: 1900 mm
diameter with insulation: 608 mm
weight: 78 kg
DHW cylinder:
nominal volume: 200 litres
material: inox AISI 444
max. operating pressure: 7 bar
max. operating temperature: 70°C
material heat exchanger: AISI 316L
heating surface coil: 2.5 m²
capacity coil: 9,2 litres
max. operating pressure coil: 3 bar
max. operating temperature coil: 85 °C
Buffer tank:
nominal volume: 80 litres
max. operating pressure: 3 bar
max. operating temperature: 85°C
min. operating temperature: -7°C
Connections DHW cylinder:
DHW: 2x DN20 (3/4")
heat exchanger: 2x DN25 (1")
circulation: DN20 (3/4")
immersion heate*r: DN32 (1 1/4")
*max. installation length: 400mm
sensor sleeve in flange top: 0.65 m
Connections buffer tank:
heating: 4x DN25 (1")
immersion heater*: DN32 (1 1/4")
*max. installation length: 440 mm
sensor: DN15 (1/2" IG), sleeve: 0,35 m
air vent: DN 10 (3/8")
Thermal insulation:
material: PU solid foam
thickness: 50 mm
protective sheath: hard shell PVC, grey
fire protection class according to
DIN 4102 for the complete insulation: B2
Standby energy consumption according to
DIN EN 12897:2020-05: 1,8 kWh/24h
standing heat loss: 75 W
energy efficiency class: C